AWG conductor resistance
DC resistance of solid copper by gauge, with the geometry it is derived from and the temperature correction that is usually left out.
Resistance by gauge at 20 °C
| Gauge | Diameter (mm) | Area (mm²) | Ω / 100 m | Ω / 1000 ft | Typical use |
|---|---|---|---|---|---|
| 22 AWG | 0.6438 | 0.3255 | 5.29 | 16.12 | Thicker horizontal cable, long PoE runs |
| 23 AWG | 0.5733 | 0.2582 | 6.68 | 20.36 | Cat 6 / Cat 6A horizontal |
| 24 AWG | 0.5106 | 0.2047 | 8.42 | 25.66 | Cat 5e / Cat 6 horizontal, most common |
| 26 AWG | 0.4049 | 0.1288 | 13.39 | 40.81 | Patch cords, stranded |
| 28 AWG | 0.3211 | 0.0810 | 21.29 | 64.89 | Slim patch cords, high-density panels |
How these are derived
Diameter follows the AWG definition, where each three gauge numbers roughly halve the area:
Resistance then follows from resistivity and geometry, with ρ = 1.724×10−8 Ω·m for annealed copper at 20 °C:
Temperature correction
Copper resistance rises about 0.393 % per °C. This is the correction people most often skip, and it is worth 16 % between a bench measurement and a cable in a hot ceiling void.
| Temperature | 22 AWG | 23 AWG | 24 AWG | 26 AWG | 28 AWG |
|---|---|---|---|---|---|
| 0 °C | 4.87 | 6.15 | 7.76 | 12.34 | 19.62 |
| 20 °C | 5.29 | 6.68 | 8.42 | 13.39 | 21.29 |
| 40 °C | 5.71 | 7.21 | 9.08 | 14.44 | 22.96 |
| 60 °C | 6.12 | 7.73 | 9.74 | 15.49 | 24.64 |
| 80 °C | 6.54 | 8.26 | 10.41 | 16.55 | 26.31 |
All values in Ω per 100 m per conductor.
Solid and stranded
Stranded conductors present roughly 1.05× the resistance of solid for the same nominal gauge, because the individual strands take a helical path and the effective copper area is lower. Patch cords are stranded; horizontal cable is solid.
Nominal versus specification limit
The figures above are nominal copper. Cabling standards permit worse: the TIA limit for a 24 AWG horizontal conductor is 9.38 Ω/100 m against the 8.42 Ω nominal, around 11 % higher. Design against the limit when you do not know what cable you are getting.
Related tool: PoE voltage drop and power budget, which uses these figures with the loop geometry of 802.3af, 802.3at and 802.3bt.