Twisted pair cable attenuation

Attenuation per 100 m by frequency and category, and the three-term law behind it — each term a different physical loss mechanism.

Attenuation per 100 m at 20 °C

f (MHz)Category 6Category 5eCategory 6A
12.042.132.08
43.814.013.80
105.996.335.93
167.608.057.49
208.529.038.38
31.2510.7411.4110.50
62.515.4816.5214.99
10019.9221.3519.13
12522.49—21.51
15525.31—24.09
20029.15—27.58
25033.04—31.07
300——34.27
400——40.05
500——45.26

Values in dB per 100 m of solid horizontal cable. A dash means the frequency is above that category's specified range, where the coefficients are not valid.

The three-term law

α(f) = a√f + b·f + c/√f   (dB per 100 m, f in MHz)

Each term is a different mechanism. The √f term is copper loss from skin effect, which dominates across the band. The linear term is dielectric loss in the insulation. The 1/√f term accounts for the shield where one is present and is negligible above a few megahertz.

CategoryabcSpecified toProvenance
Category 61.82000.01700.20250 MHzVerified against a public source
Category 5e1.91080.02220.20100 MHzUnverified, see note
Category 6A1.82000.00910.25500 MHzUnverified, see note

Where these come from

This page is sourced differently from most of this site. TIA-568 and ISO 11801 are paid standards, so nothing here is quoted from them. Category 6 coefficients come from public IEEE 802.3 working-group documents, which reproduce the cabling specification for the benefit of the Ethernet standards work. Category 5e and Category 6A are widely published figures that could not be verified against a primary source, and are labelled that way rather than presented as equal. Your cable's datasheet beats all of them.

From cable to channel

A channel is the sum of its parts. Stranded cordage loses up to 50 % more per metre than solid horizontal cable, which is where the familiar 1.05 channel factor comes from: the standard 90 m + 10 m model is electrically 90 + 10×1.5 = 105 m of cable.

IL = α(f)·Lcable/100 + α(f)·1.5·Lcords/100 + N·k√f

Temperature

Insertion loss rises roughly 0.4 %/°C for unscreened constructions and about half that for screened ones. A cable in a hot ceiling void at 60 °C carries about 16 % more insertion loss than the same cable certified on a cool day. A bundle carrying PoE heats itself, so the temperature to design against is not the ambient one.

Related tools: Channel loss and crosstalk headroom and PoE voltage drop.