Twisted pair cable attenuation
Attenuation per 100 m by frequency and category, and the three-term law behind it — each term a different physical loss mechanism.
Attenuation per 100 m at 20 °C
| f (MHz) | Category 6 | Category 5e | Category 6A |
|---|---|---|---|
| 1 | 2.04 | 2.13 | 2.08 |
| 4 | 3.81 | 4.01 | 3.80 |
| 10 | 5.99 | 6.33 | 5.93 |
| 16 | 7.60 | 8.05 | 7.49 |
| 20 | 8.52 | 9.03 | 8.38 |
| 31.25 | 10.74 | 11.41 | 10.50 |
| 62.5 | 15.48 | 16.52 | 14.99 |
| 100 | 19.92 | 21.35 | 19.13 |
| 125 | 22.49 | — | 21.51 |
| 155 | 25.31 | — | 24.09 |
| 200 | 29.15 | — | 27.58 |
| 250 | 33.04 | — | 31.07 |
| 300 | — | — | 34.27 |
| 400 | — | — | 40.05 |
| 500 | — | — | 45.26 |
Values in dB per 100 m of solid horizontal cable. A dash means the frequency is above that category's specified range, where the coefficients are not valid.
The three-term law
Each term is a different mechanism. The √f term is copper loss from skin effect, which dominates across the band. The linear term is dielectric loss in the insulation. The 1/√f term accounts for the shield where one is present and is negligible above a few megahertz.
| Category | a | b | c | Specified to | Provenance |
|---|---|---|---|---|---|
| Category 6 | 1.8200 | 0.0170 | 0.20 | 250 MHz | Verified against a public source |
| Category 5e | 1.9108 | 0.0222 | 0.20 | 100 MHz | Unverified, see note |
| Category 6A | 1.8200 | 0.0091 | 0.25 | 500 MHz | Unverified, see note |
Where these come from
This page is sourced differently from most of this site. TIA-568 and ISO 11801 are paid standards, so nothing here is quoted from them. Category 6 coefficients come from public IEEE 802.3 working-group documents, which reproduce the cabling specification for the benefit of the Ethernet standards work. Category 5e and Category 6A are widely published figures that could not be verified against a primary source, and are labelled that way rather than presented as equal. Your cable's datasheet beats all of them.
From cable to channel
A channel is the sum of its parts. Stranded cordage loses up to 50 % more per metre than solid horizontal cable, which is where the familiar 1.05 channel factor comes from: the standard 90 m + 10 m model is electrically 90 + 10×1.5 = 105 m of cable.
Temperature
Insertion loss rises roughly 0.4 %/°C for unscreened constructions and about half that for screened ones. A cable in a hot ceiling void at 60 °C carries about 16 % more insertion loss than the same cable certified on a cool day. A bundle carrying PoE heats itself, so the temperature to design against is not the ambient one.